Product Model
2020-205

Key Features
- 1High-Performance Terminal Block: Designed for reliable connections in industrial settings.
- 2Push-in CAGE CLAMP Technology: Easy and secure termination of conductors.
- 3Rated Current: 13.5 A: Handles high currents with precision.
- 4Rated Voltage: 500 V: Ensures safe operation in various electrical systems.
- 55-Pole Configuration: Supports multiple connections with ease.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Safety information | According to EN 61984, pluggable connectors without current interrupting capacity must not be mated or unmated when live or under load. | Safety information 2 | Notice: An appropriate end plate must be applied to the carrier terminal blocks after each female plug. |
| Clamping units | 10 | Total number of potentials | 5 |
| Width | 18.2?mm?/ 0.717?inches | Height | 40.5?mm?/ 1.594?inches |
| Depth | 25?mm?/ 0.984?inches | Module width | 3.5?mm?/ 0.138?inches |
| Variable coding | Yes | Marking level | Side marking |
| Anti-rotation protection | Yes | Contact type (pluggable connector) | Female connector/socket |
| Connector (connection type) | for conductor | Mismating protection | No |
| Plugging without loss of pin spacing | No | Note (material data) | Information on material specifications can be found here |
| Color | gray | Material group | I |
| Insulation material (main housing) | Polyamide (PA66) | Flammability class per UL94 | V0 |
| Fire load | 0.236MJ | Weight | 14.1g |
| Processing temperature | -35 … +85?°C | Continuous operating temperature | -60 … +105?°C |
| Product Group | 18 (X-COM-System) | eCl@ss 10.0 | 27-14-11-06 |
| eCl@ss 9.0 | 27-14-11-06 | ETIM 9.0 | EC001284 |
| ETIM 8.0 | EC001284 | ECCN | NO US CLASSIFICATION |
| PU (SPU) | 50?pcs | Packaging type | Box |
| Country of origin | DE | GTIN | 4045454855277 |
| Customs tariff number | 8536694040 | RoHS Compliance Status | Compliant,No Exemption |
| Ratings per | IEC/EN 61984 | Rated voltage (III / 3) | 500V |
| Rated impulse voltage (III / 3) | 6kV | Rated current | 13.5A |
| Legend (ratings) | (III / 3) ? Overvoltage category III / Pollution degree 3 | Approvals per | CSA 22.2 No 158 |
| Rated voltage UL (Use Group B) | 300V | Rated current UL (Use Group B) | 15A |
| Rated voltage UL (Use Group C) | 300V | Rated current UL (Use Group C) | 15A |
| Rated voltage UL (Use Group D) | 300V | Rated current UL (Use Group D) | 15A |
| Rated voltage CSA (Use Group B) | 300V | Rated current CSA (Use Group B) | 10A |
| Rated voltage CSA (Use Group C) | 300V | Rated current CSA (Use Group C) | 10A |
| Rated voltage CSA (Use Group D) | 300V | Rated current CSA (Use Group D) | 10A |
| Connection technology | Push-in CAGE CLAMP? | Actuation type | Operating tool |
| Connectable conductor materials | Copper | Nominal cross-section | 1 mm2 |
| Solid conductor | 0.14 … 1.5?mm2?/ 24 … 16?AWG | Solid conductor; push-in termination | 0.5 … 1.5?mm2?/ 20 … 16?AWG |
| Fine-stranded conductor | 0.14 … 1.5?mm2?/ 24 … 16?AWG | Fine-stranded conductor; with insulated ferrule | 0.14 … 0.75?mm2?/ 24 … 18?AWG |
| Fine-stranded conductor; with ferrule; push-in termination | 0.5 … 0.75?mm2?/ 20 … 18?AWG | Note (conductor cross-section) | Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination. |
| Strip length | 9 … 11?mm?/ 0.35 … 0.43?inches | Number of poles | 5 |
| Wiring direction | Front-entry wiring | Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment | DIN EN 50155 (VDE 0115-200):2022-06 |
| Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests | DIN EN 61373 (VDE 0115-0106):2011-04 | Spectrum/Installation location | Service life test, Category?1, Class?A/B |
| Function test with noise-like vibration | Test passed according to Section 8 of the standard | Frequency | f1= 5 Hz to f2= 150 Hz |
| Acceleration | 5g (highest test level used for all axes) | Test duration per axis | 5 h |
| Test directions | X, Y and Z axes | Monitoring for contact faults/interruptions | Passed |
| Voltage drop measurement before and after each axis | Passed | Simulated service life test through increased levels of noise-like vibration | Test passed according to Section 9 of the standard |
| Extended test scope: Monitoring for contact faults/interruptions | Passed | Extended test scope: Voltage drop measurement before and after each axis | Passed |
| Shock test | Test passed according to Section 10 of the standard | Shock form | Half sine |
| Shock duration | 30 ms | Number of shocks per axis | 3 pos. und 3 neg. |
| Vibration and shock stress for rolling stock equipment | Passed |
Specifications may be subject to change without notice