Product Model
XB6ECW6J1P

Key Features
- 1Ø16mm flush spring return design for space-saving installations.
 - 2Blue illumination ensures clear visibility in low-light conditions.
 - 3Polarized 12VDC operation for reliable performance.
 - 41NO/1NC contact configuration for versatile use.
 - 5Built to withstand demanding environments with a 2-year warranty.
 
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value | 
|---|---|---|---|
| Range of Product | Harmony XB6E  | Product or Component Type | Illuminated monolithic push-button  | 
| Device short name | XB6E  | Bezel material | Plastic  | 
| Mounting diameter | 0.6 in (16 mm)  | Sale per indivisible quantity | 5  | 
| Shape of signaling unit head | Square  | Type of operator | spring return  | 
| Operator profile | Blue flush  | Contacts type and composition | 1 C/O  | 
| Contact operation | Snap action  | Connections - terminals | Insulated faston 2.8 x 0.5 mm<br />Solder terminal <= 0.75 mm² AWG 19<br />Fast connector socket  | 
| Contacts material | Gold-flashed silver  | Light source | Integral LED  | 
| [Us] rated supply voltage | 12 V DC polarised  | Net Weight | 0.013 lb(US) (0.006 kg)  | 
| Operating position | Any position  | marking | CE  | 
| Mechanical durability | 1000000 cycles  | Contact resistance | 50 mOhm 1/6 V  | 
| Short-circuit protection | 2 A cartridge fuse gG  | [Ith] conventional free air thermal current | 3 A fast connector socket)<br />5 A  | 
| [Ie] rated operational current | 1.5 A 120 V, AC-12 IEC 60947-5-1<br />1 A 240 V, AC-12 IEC 60947-5-1<br />1 A 24 V, DC-12 IEC 60947-5-1<br />0.7 A 24 V, DC-13 IEC 60947-5-1<br />0.2 A 125 V, DC-12 IEC 60947-5-1<br />0.15 A 125 V, DC-13 IEC 60947-5-1  | Electrical durability | 100000 cycles, AC, 0.7 A 220 V IEC 60947-5-1 appendix C  | 
| Signalling type | Steady  | current consumption | 10 mA  | 
| Service life | 30000 h  | Ambient Air Temperature for Storage | -40…158 °F (-40…70 °C)  | 
| Ambient Air Temperature for Operation | 14…131 °F (-10…55 °C)  | IP degree of protection | IP65 IEC 60529  | 
| Standards | JIS C 4520<br />IEC 60947-1<br />CSA C22.2 No 14<br />JIS C 852<br />UL 508<br />IEC 60947-5-1  | Product Certifications | CCC<br />cURus  | 
| Vibration resistance | 1 mm 10…55 Hz)IEC 60068-2-6  | Shock resistance | 10 gn 11 ms) half sine wave acceleration IEC 60068-2-27  | 
Specifications may be subject to change without notice