Product Model
LC1D0983ED

Key Features
- 1Highly Reliable Contactor: The LC1D0983ED TeSys D Contactor ensures reliable operation with its 4P(2 NO + 2 NC) contact configuration.
- 2Wide Voltage Compatibility: Compatible with AC-1 ratings up to 440 V and 20 A, making it versatile for various applications.
- 3Efficient DC Coil Operation: Powered by a 48 V DC coil, this contactor offers efficient control and operation.
- 4Compliant with International Standards: Meets IEC 60947-4-1 and CSA/UL certifications for safety and performance.
- 5Compact Design for Easy Installation: Designed for easy integration into control systems, enhancing overall system efficiency and reliability.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range | TeSys | Range of Product | TeSys Deca |
| Product or Component Type | Contactor | Device short name | LC1D |
| Contactor application | Resistive load | Utilisation category | AC-1 |
| Poles description | 4P | [Ue] rated operational voltage | Power circuit <= 690 V AC 25...400 Hz<br />Power circuit <= 300 V DC |
| [Ie] rated operational current | 20 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit | [Uc] control circuit voltage | 48 V DC |
| compatibility code | LC1D | Pole contact composition | 2 NO + 2 NC |
| Protective cover | With | [Ith] conventional free air thermal current | 25 A (at 140 °F (60 °C)) for power circuit<br />10 A (at 140 °F (60 °C)) for signalling circuit |
| Irms rated making capacity | 250 A at 440 V for power circuit conforming to IEC 60947<br />140 A AC for signalling circuit conforming to IEC 60947-5-1<br />250 A DC for signalling circuit conforming to IEC 60947-5-1 | Rated breaking capacity | 250 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 105 A 104 °F (40 °C) - 10 s for power circuit<br />210 A 104 °F (40 °C) - 1 s for power circuit<br />30 A 104 °F (40 °C) - 10 min for power circuit<br />61 A 104 °F (40 °C) - 1 min for power circuit<br />100 A - 1 s for signalling circuit<br />120 A - 500 ms for signalling circuit<br />140 A - 100 ms for signalling circuit | Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1<br />25 A gG at <= 690 V coordination type 1 for power circuit<br />20 A gG at <= 690 V coordination type 2 for power circuit |
| Average impedance | 2.5 mOhm - Ith 25 A 50 Hz for power circuit | Power dissipation per pole | 1.56 W AC-1 |
| [Ui] rated insulation voltage | Power circuit 690 V IEC 60947-4-1<br />Power circuit 600 V CSA<br />Power circuit 600 V UL<br />Signalling circuit 690 V IEC 60947-1<br />Signalling circuit 600 V CSA<br />Signalling circuit 600 V UL | Overvoltage category | III |
| Pollution degree | 3 | [Uimp] rated impulse withstand voltage | 6 kV IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 | Mechanical durability | 30 Mcycles |
| Electrical durability | 0.6 Mcycles 25 A AC-1 <= 440 V | Control circuit type | DC standard |
| Coil technology | Built-in bidirectional peak limiting diode suppressor | Control circuit voltage limits | 0.1...0.25 Uc -40…158 °F (-40…70 °C) drop-out DC<br />0.7...1.25 Uc -40…140 °F (-40…60 °C) operational DC<br />1...1.25 Uc 140…158 °F (60…70 °C) operational DC |
| Inrush power in W | 5.4 W 68 °F (20 °C)) | Hold-in power consumption in W | 5.4 W 68 °F (20 °C) |
| Operating time | 63 ±15 % ms closing<br />20 ±20 % ms opening | Time constant | 28 ms |
| Maximum operating rate | 3600 cyc/h at 60 °C | Connections - terminals | Power circuit: spring terminals 1 0.004 in² (2.5 mm²) - cable stiffness: flexible without cable end<br />Power circuit: spring terminals 2 0.004 in² (2.5 mm²) - cable stiffness: flexible without cable end<br />Control circuit: spring terminals 1 0.004 in² (2.5 mm²) - cable stiffness: flexible without cable end<br />Control circuit: spring terminals 2 0.004 in² (2.5 mm²) - cable stiffness: flexible without cable end |
| Auxiliary contact composition | 1 NO + 1 NC | Auxiliary contacts type | Mechanically linked 1 NO + 1 NC IEC 60947-5-1<br />Mirror contact 1 NC IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz | Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit | Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact<br />1.5 ms on energisation between NC and NO contact | Mounting Support | Plate<br />Rail |
| Standards | CSA C22.2 No 14<br />EN 60947-4-1<br />EN 60947-5-1<br />IEC 60947-4-1<br />IEC 60947-5-1<br />UL 508 | Product Certifications | CSA<br />BV<br />GL<br />CCC<br />DNV<br />LROS (Lloyds register of shipping)<br />RINA<br />UL<br />GOST |
| IP degree of protection | IP20 front face IEC 60529 | Protective treatment | THIEC 60068-2-30 |
| Climatic withstand | IACS E10 exposure to damp heat<br /> IEC 60947-1 Annex Q category D exposure to damp heat | Permissible ambient air temperature around the device | -40…140 °F (-40…60 °C)<br />140…158 °F (60…70 °C) with derating |
| Operating altitude | 0...9842.52 ft (0...3000 m) | Fire resistance | 1562 °F (850 °C) IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 | Mechanical robustness | Vibrations contactor open 2 Gn, 5...300 Hz) <br />Vibrations contactor closed 4 Gn, 5...300 Hz) <br />Shocks contactor open 10 Gn for 11 ms) <br />Shocks contactor closed 15 Gn for 11 ms) |
| Height | 3.3 in (85 mm) | Width | 1.8 in (45 mm) |
| Depth | 3.9 in (99 mm) | Net Weight | 1.157 lb(US) (0.525 kg) |
Specifications may be subject to change without notice