Product Model
140DDO84300

Key Features
- 1Versatile 16-Channel Configuration: The 140DDO84300 features two groups of eight discrete outputs, ensuring efficient organization and distribution in complex systems.
- 2Wide Voltage Range: Operates between 10-60V DC with an absolute maximum output of 72V, making it suitable for a range of DC-powered systems.
- 3Robust Isolation: Provides 700Vrms DC isolation between groups and 2500Vrms DC isolation between channels and the bus, enhancing safety and preventing interference.
- 4High-Performance Protection: Equipped with internal output protection by 8A fuses per group, safeguarding against overcurrent and short-circuit conditions.
- 5Efficient Power Consumption: Low power dissipation of 1W plus additional calculation based on total module load current, minimizing heat buildup and ensuring energy efficiency.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | Modicon Quantum automation platform | Product or Component Type | Dc discrete output module |
| Discrete output number | 16 | Group of channels | 2 groups of 8 |
| Discrete output logic | Positive logic (source) | Addressing requirement | 1 output word |
| Discrete output voltage | 10...60 V DC | Output voltage limits | 10.2...72 V |
| Absolute maximum output | 72 V permanent | Maximum voltage drop | <1 V 2 A |
| Maximum load current | 12 A per module<br />6 A per group | Surge current | 7.5 A 50 s |
| Response Time | <= 1 ms at state 0 to state 1<br /><= 1 ms at state 1 to state 0 | Maximum leakage current | 1 mA 60 V |
| Load inductance | Inductance(H) = 0.5/((current(A))² x (switching frequency(Hz))) | Associated fuse rating | 2 A each point<br />8 A per group |
| Isolation between channels and bus | 2500 Vrms DC for 1 minute | Isolation between group | 700 Vrms DC for 1 minute |
| Protection Type | Internal output protection by 8 A fuse per group | Power dissipation | 1 W + (1 V x total module load current) |
| marking | CE | Local signalling | for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 16 LEDs (green) |
| Bus current requirement | 160 mA | Module format | Standard |
| Net Weight | 0.99 lb(US) (0.45 kg) | Product Certifications | GOST<br />RMRS<br />FM Class 1 Division 2<br />C-tick |
| Standards | CSA C22.2 No 142<br />UL 508 | Resistance to electrostatic discharge | 4 kV contact IEC 801-2<br />8 kV on air IEC 801-2 |
| Resistance to electromagnetic fields | 9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3 | Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) |
| Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) | Relative Humidity | 95 % without condensation |
| Operating altitude | <= 16404.2 ft (5000 m) |