Product Model
RIF-1-RSC-LV-120AC/2X21AU

Key Features
- 1High-Power Protection: Designed for high-power applications with a maximum inrush current of 12 A and interrupting rating up to 2000 VA.
- 2Safe Isolation: Ensures safe isolation between input and output with basic insulation between changeover contacts.
- 3Robust Technical Specifications: Operates at 120 V AC with a typical input current of 8 mA and response time of 3 ms to 12 ms.
- 4Durable Construction: Made with AgNi, hard gold-plated contacts for long-lasting performance and resistance to corrosion.
- 5Comprehensive Certifications: Meets CB Scheme (IEC 60947-5-1) standards and has a flammability rating of V2 according to UL 94.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Notes on operation | FBS 2-6... plug-in bridge for the input side (A2) and FBS-2-8... plug-in bridge for the output side (11/21) | Product type | Relay Module |
| Product family | RIFLINE complete | Application | Universal |
| Operating mode | 100% operating factor | Mechanical service life | approx. 10 |
| Date of last data management | 21.08.2024 | Article revision | 05 |
| Insulation | Safe isolation between input and output
Basic insulation between the changeover contacts | Overvoltage category | III |
| Pollution degree | 2 | Service life electrical | see diagram |
| Maximum power dissipation for nominal condition | 0.96 W | Test voltage (Winding/contact) | 4 kV |
| Test voltage (Changeover contact/changeover contact) | 2.5 kV | Rated insulation voltage | 250 V AC |
| Rated surge voltage | 6 kV (Input/output)
4 kV (between the changeover contacts) | Nominal input voltage U | 120 V AC |
| Input voltage range | 96 V AC ... 138 V AC (20 °C) | Input voltage range in reference to U | see diagram |
| Mains frequency | 50/60 Hz | Drive and function | monostable |
| Drive (polarity) | polarized | Typical input current at U | 8 mA |
| Typical response time | 3 ms ... 12 ms | Typical release time range | 3 ms ... 20 ms |
| Coil voltage | 120 V AC | Protective circuit | Varistor |
| Operating voltage display | Yellow LED | Contact switching type | 2 changeover contacts |
| Type of switch contact | Single contact | Contact material | AgNi, hard gold-plated |
| Maximum switching voltage | 30 V AC
36 V DC | Minimum switching voltage | 100 mV (at 10 mA) |
| Limiting continuous current | 50 mA | Maximum inrush current | 50 mA |
| Min. switching current | 1 mA (24 V) | Interrupting rating (ohmic load) max. | 1.2 W (at 24 V DC) |
| Utilization category CB Scheme (IEC 60947-5-1) | AC15, 1.5 A/240 V (N/O contact)
AC15, 2 A/250 V (N/C contact)
DC13, 2 A/24 V (N/C contact)
DC13, 0.2 A/250 V (N/O contact) | Note | — |
| Contact material | AgNi | Maximum switching voltage | 250 V AC/DC |
| Minimum switching voltage | 5 V (at 10 mA) | Maximum inrush current | 12 A (20 ms, N/O contacts) |
| Min. switching current | 10 mA (At 5 V) | Interrupting rating (ohmic load) max. | 192 W (at 24 V DC)
96 W (at 48 V DC)
60 W (at 60 V DC)
44 W (at 110 V DC)
57 W (at 220 V DC)
2000 VA (for 250 V AC) |
| Switching capacity | 2 A (at 24 V, DC13)
0.2 A (at 110 V, DC13)
0.2 A (at 250 V, DC13)
2 A (at 24 V, AC15)
2 A (at 120 V, AC15)
2 A (at 250 V, AC15) | Connection method | Screw connection |
| Stripping length | 8 mm | Conductor cross section rigid | 0.5 mm² ... 4 mm² |
| Conductor cross-section rigid (2 conductors with same cross section) | 0.5 mm² ... 2.5 mm² | Conductor cross section flexible | 0.5 mm² ... 4 mm²
0.5 mm² ... 4 mm² (Ferrule with plastic sleeve) |
| Conductor cross section flexible (2 conductors with same cross section) | 0.5 mm² ... 2.5 mm²
0.5 mm² ... 1.5 mm² (TWIN ferrule with plastic sleeve) | Conductor cross section AWG | 20 ... 10 (solid)
20 ... 12 (flexible) |
| Tightening torque | 0.5 Nm ... 0.6 Nm | Width | 16 mm |
| Height | 90 mm | Depth | 75 mm |
| Color | gray (RAL 7042) | Flammability rating according to UL 94 | V2 (Housing) |
| Degree of protection (Relay base) | IP20 (Relay base) | Degree of protection (Relay) | RT III (Relay) |
| Ambient temperature (operation) | -40 °C ... 50 °C | Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Identification | ISA-S71.04. G3 Harsh Group
EN 60068-2-60 | Standards/regulations | IEC 60947-5-1 |
| Mounting type | DIN rail mounting | Assembly note | in rows with zero spacing |
| Mounting position | any |
Specifications may be subject to change without notice