Product Model
RIF-1-RPT-LV-120AC/1X21AU

Key Features
- 1Supports up to 250 V AC/DC with a minimum switching voltage of 12 V.
 - 2Constructed with AgNi material for long-lasting performance.
 - 3Measures 16 mm in width, 93 mm in height, and 75 mm in depth.
 - 4Operates between -40 °C and 50 °C ambient temperature.
 - 5Suitable for various electrical control applications with a monostable drive function.
 
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value | 
|---|---|---|---|
| Notes on operation | FBS 2-6... plug-in bridge for the input side (A2) and FBS-2-8... plug-in bridge for the output side (11/21)  | Product type | Relay Module  | 
| Product family | RIFLINE complete  | Application | Universal  | 
| Operating mode | 100% operating factor  | Mechanical service life | approx. 10  | 
| Date of last data management | 10.06.2024  | Article revision | 05  | 
| Insulation | Safe isolation between input and output
Basic insulation between the changeover contacts  | Overvoltage category | III  | 
| Pollution degree | 2  | Service life electrical | see diagram  | 
| Maximum power dissipation for nominal condition | 0.96 W  | Test voltage (Winding/contact) | 4 kV  | 
| Rated insulation voltage | 250 V AC  | Rated surge voltage | 6 kV (Input/output)
4 kV (between the changeover contacts)  | 
| Nominal input voltage U | 120 V AC  | Input voltage range | 96 V AC ... 138 V AC (20 °C)  | 
| Input voltage range in reference to U | see diagram  | Mains frequency | 50/60 Hz  | 
| Drive and function | monostable  | Typical input current at U | 8 mA  | 
| Typical response time | 3 ms ... 12 ms  | Typical release time range | 3 ms ... 20 ms  | 
| Coil voltage | 120 V AC  | Protective circuit | Varistor  | 
| Operating voltage display | Yellow LED  | Contact switching type | 1 changeover contact  | 
| Type of switch contact | Single contact  | Contact material | AgNi, hard gold-plated  | 
| Maximum switching voltage | 30 V AC
36 V DC  | Minimum switching voltage | 100 mV (10 mA)  | 
| Limiting continuous current | 50 mA  | Maximum inrush current | 50 mA  | 
| Min. switching current | 1 mA (24 V)  | Interrupting rating (ohmic load) max. | 1.2 W (24 V DC)  | 
| Utilization category CB Scheme (IEC 60947-5-1) | AC15, 1.5 A/240 V (N/O contact)
AC15, 3 A/250 V (N/C contact)
DC13, 2 A/24 V (N/C contact)
DC13, 0.2 A/250 V (N/O contact)  | Note | —  | 
| Contact material | AgNi  | Maximum switching voltage | 250 V AC/DC  | 
| Minimum switching voltage | 12 V (at 10 mA)  | Limiting continuous current | 25 A (20 ms, N/O contacts)  | 
| Min. switching current | 10 mA (at 12 V)  | Interrupting rating (ohmic load) max. | 240 W (at 24 V DC)
58 W (at 48 V DC)
48 W (at 60 V DC)
50 W (at 110 V DC)
80 W (at 220 V DC)
2500 VA (for 250 V AC)  | 
| Switching capacity | 2 A (at 24 V, DC13)
0.2 A (at 110 V, DC13)
0.2 A (at 250 V, DC13)
2 A (at 24 V, AC15)
2 A (at 120 V, AC15)
2 A (at 250 V, AC15)  | Connection method | Push-in connection  | 
| Stripping length | 8 mm  | Conductor cross section rigid | 0.14 mm² ... 1.5 mm²  | 
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm²
0.14 mm² ... 1.5 mm² (Ferrule with plastic sleeve)
0.14 mm² ... 1 mm² (Ferrule with plastic sleeve, two conductors on double terminal block)  | Conductor cross section AWG | 26 ... 16 (solid)
26 ... 16 (flexible)  | 
| Diameter | 3.2 mm  | Width | 16 mm  | 
| Height | 93 mm  | Depth | 75 mm  | 
| Color | gray (RAL 7042)  | Flammability rating according to UL 94 | V2 (Housing)  | 
| Degree of protection (Relay base) | IP20 (Relay base)  | Degree of protection (Relay) | RT II (Relay)  | 
| Ambient temperature (operation) | -40 °C ... 50 °C  | Ambient temperature (storage/transport) | -40 °C ... 85 °C  | 
| Identification | ISA-S71.04. G3 Harsh Group
EN 60068-2-60  | Standards/regulations | DIN EN 50178  | 
| Mounting type | DIN rail mounting  | Assembly note | in rows with zero spacing  | 
| Mounting position | any  | 
Specifications may be subject to change without notice