Product Model
RIF-0-OPT-24DC/24DC/2

Key Features
- 1Designed for industrial use with a high operating factor and robust construction.
- 2Measures 6.2 mm wide, 93 mm high, and 66 mm deep, ideal for space-constrained environments.
- 3Operates between -25°C to 60°C ambient temperature, ensuring flexibility in various conditions.
- 4Offers a typical response time of 20 µs and turn-off time of 300 µs for fast and reliable switching.
- 5Includes free-wheeling diode and surge voltage protection up to 4 kV AC for enhanced safety.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Product type | Solid-state relay module | Product family | RIFLINE complete |
| Application | Universal | Operating mode | 100% operating factor |
| Date of last data management | 10.06.2024 | Article revision | 06 |
| Insulation | Basic insulation | Overvoltage category | III |
| Pollution degree | 2 | Maximum power dissipation for nominal condition | 0.2 W |
| Test voltage (Input/output) | 2.5 kV | Rated insulation voltage | 250 V AC |
| Rated surge voltage | 4 kV | Rated actuating voltage U | 24 V DC |
| Voltage range with reference to U | 0.8 ... 1.2 | Rated actuating current I | 8.5 mA |
| Input voltage range | 19.2 V DC ... 28.8 V DC | "0" signal switching threshold in reference to U | < 0.4 |
| "1" signal switching threshold in reference to U | > 0.8 | Typical response time | 20 µs |
| Typical turn-off time | 300 µs | Status display | LED (yellow) |
| Protective circuit | Freewheeling diode | Transmission frequency | 300 Hz |
| Contact switching type | 1 N/O contact | Design of digital output | electronic |
| Output voltage range | 3 V DC ... 33 V DC | Limiting continuous current | 3 A (see derating curve) |
| Maximum inrush current | 15 A (10 ms) | Surge voltage protection | > 33 V |
| Voltage drop at max. limiting continuous current | < 200 mV | Output circuit | 2-conductor, floating |
| Protective circuit | Reverse polarity protection
Surge protection | Utilization category CB Scheme (IEC 60947-5-1) | DC12, 3 A/24 V |
| Connection method | Push-in connection | Stripping length | 8 mm |
| Conductor cross section rigid | 0.14 mm² ... 1.5 mm² | Conductor cross section flexible | 0.14 mm² ... 1.5 mm²
0.14 mm² ... 1.5 mm² (Ferrule with plastic sleeve) |
| Conductor cross section AWG | 24 ... 16 | Width | 6.2 mm |
| Height | 93 mm | Depth | 66 mm |
| Color | gray (RAL 7042) | Flammability rating according to UL 94 | V2 (Housing) |
| Degree of protection | IP20 | Ambient temperature (operation) | -25 °C ... 60 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C | Identification | ISA-S71.04. G3 Harsh Group
EN 60068-2-60 |
| Standards/regulations | DIN EN 60947-5-1 | Mounting type | DIN rail mounting |
| Assembly note | in rows with zero spacing | Mounting position | any |
Specifications may be subject to change without notice