Product Model
RIF-0-OPT-24DC/230AC/1

Key Features
- 1Vibration and shock resistant: Designed to withstand harsh environmental conditions.
- 2Zero voltage switch: Ensures safe switching at AC output.
- 3Wear-free and durable: Long-lasting performance with minimal maintenance.
- 4Wide input voltage range: Operates between 19.2 V DC and 28.8 V DC.
- 5Compact design: Measuring 5 mm x 28 mm x 15 mm, perfect for PCB mounting.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Product type | Solid-state relay module | Product family | RIFLINE complete |
| Application | Universal | Operating mode | 100% operating factor |
| Date of last data management | 10.06.2024 | Article revision | 06 |
| Insulation | Basic insulation | Overvoltage category | III |
| Pollution degree | 2 | Maximum power dissipation for nominal condition | 0.19 W |
| Test voltage (Input/output) | 2.5 kV | Rated insulation voltage | 250 V AC |
| Rated surge voltage | 4 kV | Rated actuating voltage U | 24 V DC |
| Voltage range with reference to U | 0.8 ... 1.2 | Rated actuating current I | 8 mA |
| Input voltage range | 19.2 V DC ... 28.8 V DC | "0" signal switching threshold in reference to U | < 0.4 |
| "1" signal switching threshold in reference to U | > 0.8 | Typical response time | 10 ms |
| Typical turn-off time | 10 ms | Status display | LED (yellow) |
| Protective circuit | Freewheeling diode | Transmission frequency | 10 Hz |
| Contact switching type | 1 N/O contact | Design of digital output | electronic |
| Output voltage range | 24 V AC ... 253 V AC (50/60 Hz) | Limiting continuous current | 750 mA (see derating curve) |
| Maximum inrush current | 30 A (10 ms) | Min. load current | 10 mA |
| Leakage current | 1 mA (in off state) | Surge current | 30 A AC (tp = 20 ms, at 25 °C) |
| Phase angle cos phi min | 0.5 | Max. load value | 4.5 A |
| Surge voltage protection | > 275 V | Voltage drop at max. limiting continuous current | < 1 V |
| Output circuit | 2-conductor, zero voltage switch | Protective circuit | RCV circuit |
| Utilization category CB Scheme (IEC 60947-5-1) | AC12, 0.75 A/250 V | Connection method | Push-in connection |
| Stripping length | 8 mm | Conductor cross section rigid | 0.14 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm²
0.14 mm² ... 1.5 mm² (Ferrule with plastic sleeve) | Conductor cross section AWG | 24 ... 16 |
| Width | 6.2 mm | Height | 93 mm |
| Depth | 66 mm | Color | gray (RAL 7042) |
| Flammability rating according to UL 94 | V2 (Housing) | Degree of protection | IP20 |
| Ambient temperature (operation) | -25 °C ... 60 °C | Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Identification | ISA-S71.04. G3 Harsh Group
EN 60068-2-60 | Standards/regulations | DIN EN 60947-5-1 |
| Mounting type | DIN rail mounting | Assembly note | in rows with zero spacing |
| Mounting position | any |
Specifications may be subject to change without notice