Product Model
RAD-ISM-2400-RX

Key Features
- 1Trusted Wireless Technology: Utilizes frequency hopping for secure and reliable data transmission.
- 2License-Free Operation: Operates on the 2.4 GHz ISM band without the need for a license.
- 3No Parameterization Required: Easy setup with no programming or parameterization needed.
- 4Industrial-Grade Reliability: Designed for harsh environments with extended temperature range (-40°C to 70°C).
- 5Advanced Signal Processing: Detects digital and analog signals (5-30 V AC/DC, 4-20 mA) for precise data processing.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Product type | Wireless module | Supply voltage | 24 V DC -50 % / +25 % (at U |
| Supply voltage range | 12 V DC ... 30 V DC | Typical current consumption | 54 mA |
| Max. current consumption | 120 mA | Output name | 2x relay output + 1 x RF link |
| Contact switching type | 3 floating changeover contacts | Contact material | Ag, gold-plated |
| Maximum switching voltage | 30 V DC
30 V AC | Limiting continuous current | 0.5 A |
| Service life electrical | 8x 10 | Mechanical service life | 1x 10 |
| Output name | Current output | Current output signal | 4 mA ... 20 mA |
| Load/output load current output | 700 Ω (at U | Connection method | Screw connection |
| Stripping length | 8 mm | Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² | Cross section AWG | 24 ... 14 |
| Screw thread | M3 | Direction | Uni-directional |
| Frequency band | 2.4 GHz | Width | 17.5 mm |
| Height | 99 mm | Depth | 114.5 mm |
| Color (Housing) | green (RAL 6021) | Material (Housing) | Polyamide |
| Degree of protection | IP20 | Degree of protection | IP20 |
| Ambient temperature (operation) | -20 °C ... 65 °C
-4 °F ... 149 °F | Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Certificate | CE-compliant | Identification | II 3 G EEx nL IIC |
| Note | Please follow the special installation instructions in the documentation! | Identification | Ex nL IIC T4 |
| Electromagnetic compatibility | Conformance with R&TTE directive 1999/5/EC | Assembly note | on standard DIN rail NS 35 in accordance with EN 60715 |
| Mounting position | any |
Specifications may be subject to change without notice