Product Model
QUINT4-UPS/24DC/24DC/20/USB/C1

Key Features
- 1Intelligent battery management with IQ Technology for superior system availability.
- 2Robust communication interfaces including USB, PROFINET, EtherNet/IP, and EtherCAT.
- 3High efficiency with up to 98% efficiency during operation.
- 4Automatic battery detection and charging with up to 5 A charging current.
- 5Reliable shutdown and restart functions to prevent data loss during power failures.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Input voltage | 24 V DC | Input voltage range | 18 V DC ... 30 V DC
18 V DC ... 32 V DC |
| Electric strength, max. | 35 V DC | Internal input fuse | no |
| Voltage type of supply voltage | DC | Inrush current | ≤ 8 A (≤ 4 ms) |
| Reverse polarity protection | yes | Fixed backup threshold | 22 V DC |
| Dynamic activation threshold | > 1 V / 100 ms | Switch-on time | max. 3 s |
| Switch-on time during battery operation (Bat.-Start) | 8 s | Voltage drop, input/output | 0.4 V DC |
| Current consumption I | 20.1 A | Current consumption I | 31.2 A |
| Current consumption I | 50 mA | Current consumption I | 6.1 A |
| Power consumption P | 474 W | Power consumption P | 738 W |
| Power consumption P | 1.3 W | Power consumption P | 145 W |
| Number of outputs | 1 | Short-circuit-proof | yes |
| No-load proof | yes | Output voltage | 24 V DC (U |
| Output voltage range | 18 V DC ... 30 V DC
18 V DC ... 32 V DC | Output current I | 20 A |
| Static Boost (I | 25 A | Dynamic Boost (I | 30 A (5 s) |
| Selective Fuse Breaking (I | 120 A (15 ms) | Output power P | 480 W |
| Output power P | 600 W | Output voltage | 24 V DC (U |
| Output voltage range | 19 V DC ... 32 V DC | Output current I | 20 A |
| Static Boost (I | 25 A | Selective Fuse Breaking (I | 120 A (15 ms) |
| Output power P | 480 W | Output power P | 600 W |
| Nominal capacity (without additional charger) | 3 Ah ... 100 Ah | Max. capacity | 135 Ah |
| Buffer time | 19 min (12 Ah) | Battery technology | VRLA, VRLA-WTR, LI-ION |
| IQ-Technology | yes | Temperature sensor | yes |
| Interface | USB (Modbus/RTU) | Number of interfaces | 1 |
| Connection method | MINI-USB Type B | Connection marking | X1 |
| Locking | Screw | Transmission physics | USB 2.0 |
| Topology | Point-to-point | Product type | DC UPS |
| Product family | QUINT USV | Environmental protection directive | RoHS Directive 2011/65/EU
WEEE
Reach |
| Protection class | III | Degree of pollution | 2 |
| Width | 40 mm | Height | 130 mm |
| Depth | 125 mm
125 mm (Device depth (DIN rail mounting)) | Width | 123 mm |
| Height | 130 mm | Depth | 42 mm |
| Installation distance right/left (active) | 5 mm / 5 mm (P | Installation distance right/left (passive) | 0 mm / 0 mm (P |
| Installation distance right/left (active, passive) | 0 mm / 0 mm (P | Installation distance top/bottom (active) | 50 mm / 50 mm (P |
| Installation distance top/bottom (passive) | 40 mm / 20 mm (P | Installation distance top/bottom (active, passive) | 40 mm / 20 mm (P |
| Mounting type | DIN rail mounting | Assembly note | alignable: horizontally 0 mm, vertically 50 mm |
| Mounting position | On horizontal DIN rail NS 35/7.5 and NS 35/15 acc. to EN 60715 | Flammability rating according to UL 94 (housing / terminal blocks) | V0 |
| Hood version | Stainless steel X6Cr17 | Side element version | Aluminum AlMg3 |
| Degree of protection | IP20 | Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C | Ambient temperature (start-up type tested) | -40 °C |
| Maximum altitude | ≤ 4000 m | Climatic class | 3K3 (EN 60721) |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) | Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | 2.3g | Standard designation | Protective extra-low voltage |
| Standards/specifications | IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV) | EMC requirements for noise emission | EN 61000-6-3
EN 61000-6-4 |
| EMC requirements for noise immunity | EN 61000-6-1
EN 61000-6-2 |
Specifications may be subject to change without notice