Product Model
PLC-RSC- 24DC/PMC T200/21HC

Key Features
- 1100% operating factor ensures consistent performance.
 - 2Reinforced insulation with safe isolation between adjacent modules.
 - 3Compatible with 19.2 V DC to 26.4 V DC input voltage range.
 - 4Typical response time of 7 ms for quick switching.
 - 5Equipped with surge protection and freewheeling diode for reliability.
 
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value | 
|---|---|---|---|
| Product type | Relay Module  | Product family | PLC-INTERFACE  | 
| Operating mode | 100% operating factor  | Mechanical service life | approx. 2x 10  | 
| Date of last data management | 08.07.2024  | Article revision | 09  | 
| Insulation | Safe isolation, reinforced insulation (partition plate PLC-ATP should be installed for safe isolation between adjacent modules).  | Overvoltage category | III  | 
| Pollution degree | 3  | Maximum power dissipation for nominal condition | 0.4 W  | 
| Nominal input voltage U | 24 V DC  | Input voltage range | 19.2 V DC ... 26.4 V DC (20 °C)  | 
| Nominal voltage (plugged-in electromechanical relay) | 24 V DC  | Typical input current at U | 15 mA (Relay ON)
4.3 mA (Relay OFF)  | 
| Typical response time | 7 ms  | Typical release time | 200 ms +130 ms (Typical interval time at U  | 
| Protective circuit | Surge protection; Freewheeling diode  | Operating voltage display | Yellow LED  | 
| Contact switching type | Single contact, 1 changeover contact  | Type of switch contact | Single contact  | 
| Contact material | AgNi, hard gold-plated  | Maximum switching voltage | 250 V AC/DC (Separating plate PLC-ATP must be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules.)  | 
| Minimum switching voltage | 12 V AC/DC  | Limiting continuous current | 10 A  | 
| Maximum inrush current | 16 A  | Min. switching current | 100 mA  | 
| Interrupting rating (ohmic load) max. | 240 W (at 24 V DC)
144 W (at 48 V DC)
48 W (at 60 V DC)
50 W (at 110 V DC)
80 W (at 220 V DC)
4000 W (for 250 V AC)  | Connection method | Screw connection  | 
| Stripping length | 8 mm  | Screw thread | M3  | 
| Conductor cross section rigid | 0.14 mm² ... 2.5 mm²  | Conductor cross section flexible | 0.14 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm² (Single ferrule)
2x 0.5 mm² ... 1.5 mm² (TWIN ferrule)  | 
| Conductor cross section AWG | 26 ... 14  | Tightening torque | 0.45 Nm ... 0.55 Nm (Usually these terminal blocks must be supported during conductor connection (held by one hand, supported on the housing))  | 
| Width | 14 mm  | Height | 80 mm  | 
| Depth | 94 mm  | Color | green (RAL 6021)  | 
| Flammability rating according to UL 94 | V0 (Housing)  | Degree of protection | IP20  | 
| Ambient temperature (operation) | -20 °C ... 50 °C  | Identification | ISA-S71.04. G3 Harsh Group
EN 60068-2-60  | 
| Standards/regulations | DIN EN 50178  | Mounting type | DIN rail mounting  | 
| Assembly note | in rows with zero spacing  | Mounting position | any  | 
Specifications may be subject to change without notice