Product Model
PLC-OSP-230AC/300DC/ 1

Key Features
- 1Wear-free switching with no contact bounce for reliable operation.
- 2Resistant to vibrations and shocks, ensuring durability in harsh environments.
- 3Protective circuit in input and output for enhanced safety.
- 4Electronic PDT output of up to 48 V DC, suitable for various industrial applications.
- 5Compact dimensions (6.2 mm x 80 mm x 86 mm) for easy integration into systems.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| EMC note | EMC: class A product, see manufacturer's declaration in the download area | Product type | Solid-state relay module |
| Product family | PLC-INTERFACE | Application | With integrated solid-state relay |
| Operating mode | 100% operating factor | Date of last data management | 27.05.2024 |
| Insulation | Basic insulation | Overvoltage category | III |
| Pollution degree | 2 | Rated insulation voltage | 300 V |
| Rated surge voltage | 2.5 kV | Nominal input voltage U | 230 V AC |
| Input voltage range in reference to U | 0.8 ... 1.1 | Input voltage range | 184 V AC ... 253 V AC |
| Switching threshold "0" signal in reference to U | ≤ 0.4 | Switching threshold "1" signal in reference to U | ≥ 0.8 |
| Typical input current at U | 8.4 mA | Typical response time | 19 ms |
| Typical turn-off time | 6 ms | Operating voltage display | Yellow LED |
| Protective circuit | Bridge rectifier; Bridge rectifier | Transmission frequency | 10 Hz |
| Designation | Output data | Contact switching type | 1 N/O contact |
| Design of digital output | electronic | Output voltage range | 12 V DC ... 300 V DC (Partition plate PLC-ATP must be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal points in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or ...FBST 500...) |
| Limiting continuous current | 1 A (see derating curve) | Voltage drop at max. limiting continuous current | < 500 mV |
| Protective circuit | Reverse polarity protection; Polarity protection diode
Surge protection; Varistor | Connection method | Spring-cage connection |
| Stripping length | 8 mm | Conductor cross section rigid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² | Conductor cross section AWG | 26 ... 14 |
| Connection method | Spring-cage connection | Stripping length | 8 mm |
| Conductor cross section rigid | 0.14 mm² ... 2.5 mm² | Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| Conductor cross section AWG | 26 ... 14 | Width | 6.2 mm |
| Height | 80 mm | Depth | 86 mm |
| Color | green (RAL 6021) | Flammability rating according to UL 94 | V0 (Housing) |
| Ambient temperature (operation) | -25 °C ... 60 °C | Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Standards/regulations | IEC 60664
EN 50178 | Assembly note | in rows with zero spacing |
| Mounting position | any |
Specifications may be subject to change without notice