Product Model
ILC 151 ETH/XC

Key Features
- 1Highly modular and adaptable to various application requirements.
- 2Integrated Ethernet interface for parameterization and programming using PC Worx automation software.
- 3Supports IEC 61131-3 programming standards for precise multi-channel controllers.
- 4Operates under harsh ambient conditions with a wide temperature range (-40°C to 60°C).
- 5Supports multiple protocols including HTTP, FTP, SNTP, SNMP, SMTP, SQL, and MySQL.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| CCCex note | Use in potentially explosive areas is not permitted in China. | Product type | Controller |
| Product family | Inline-Controller | Type | modular |
| Article revision | 13 | Diagnostics display | no |
| Processor | AlteraNios® II 64 MHz | Clock frequency | 64 MHz |
| Retentive data storage | 8 kByte (NVRAM) | Program memory | 256 kByte |
| Data storage system | 256 kByte | Number of control tasks | 8 |
| Amount of process data | max. 4096 bit (INTERBUS) | Number of supported devices | max. 128 |
| Number of local bus devices that can be connected | max. 63 (observe current consumption) | Number of devices with parameter channel | max. 16 |
| Number of supported branch terminals with remote bus branch | max. 3 | Amount of process data | max. 16384 bit (internal Modbus /TCP client) |
| Number of Modbus/TCP clients | max. 8 later than FW 4.42 | Device function | PROFINET device |
| Specification | 2.2 | Device ID | 007E |
| Vendor ID | 00B0 | Diagnostics display | no |
| Controller redundancy | no | Safety function | no |
| Programming languages supported | Instruction list (IL)
Symbolic flowchart (SFC)
Ladder diagram (LD)
Function block diagram (FBD)
Structured text (ST) | Engineering tool | PC Worx
PC Worx Express |
| Configuration tool | Config+ Version 1.01 or later | Diagnostics tool | DIAG+ |
| Runtime system | eCLR | Application interface | OPC |
| Transmission medium | Copper | Realtime clock | yes |
| Description realtime clock | not integrated | Supply voltage | 24 V DC -15 % / +20 % (in accordance with EN 61131-2) |
| Supply voltage range | 19.2 V DC ... 30 V DC | Current draw | 80 mA (without connected I/O terminal blocks) |
| Supply voltage | 7.5 V DC ±5 % | Supply voltage | 24 V DC -15 % / +20 % |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) | Supply voltage | 24 V DC -15 % / +20 % (in accordance with EN 61131-2) |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) | Current draw | max. 8 A DC
6 mA (without sensors) |
| Supply voltage | 24 V DC -15 % / +20 % (in accordance with EN 61131-2) | Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current draw | max. 8 A DC
10 mA (without actuators) | Input name | Digital inputs |
| Description of the input | EN 61131-2 type 1 NPN/PNP | Number of inputs | 8 |
| Cable length | max. 30 m | Connection method | Inline potential distributor |
| Connection technology | 2-, 3-, 4-conductor | Input voltage range | -0.5 V ... 30 V |
| Input voltage range "0" signal | -0.5 V ... 5 V | Input voltage range "1" signal | 15 V ... 30 V |
| Nominal input current at U | typ. 7 mA
max. 15 mA | Input filter time | typ. 5 ms (Signal change 01)
typ. 5 ms () |
| Output name | Digital outputs | Connection method | Spring-cage connection |
| Connection technology | 2-, 3-, 4-conductor | Number of outputs | 4 |
| Maximum output current per channel | 500 mA | Maximum output current per module / terminal block | 2 A |
| Nominal load, lamp | 12 W | Nominal load, ohmic | 12 W |
| Behavior with inductive overload | Output can be destroyed | Connection method | Spring-cage connection |
| Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² | Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 | Web server | yes |
| Bus system | RJ45 | Number of interfaces | 1 |
| Connection method | RJ45 jack | Transmission speed | 10/100 Mbps |
| No. of channels | 1 | Number of interfaces | 1 |
| Connection method | Inline data jumper | Transmission speed | 500 kBaud / 2 MBaud (can be switched) |
| Bus system | RS-232 | Number of interfaces | 1 |
| Connection method | 6-pos. MINI DIN socket (PS/2) | Transmission speed | max. 115.2 kbps |
| Transmission physics | Copper | No. of channels | 1 |
| Width | 80 mm | Height | 119.8 mm |
| Depth | 71.5 mm | Color | green (RAL 6021) |
| Degree of protection | IP20 | Ambient temperature (operation) | -40 °C ... 60 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C | Permissible humidity (operation) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Permissible humidity (storage/transport) | 10 % ... 95 % (according to DIN EN 61131-2) | Shock | 25g, Criterion 1, according to IEC 60068-2-27 |
| Vibration (operation) | 5g | Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | Resistance to gases that may endanger the functions, in acc. with DIN 40046-36, DIN 40046-37 | Sulfur dioxide (SO |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU | Conformance with EMC directives | Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Electrostatic discharge (ESD)EN 61000-4-2/IEC 61000-4-2 Criterion B, ±6 kV contact discharge, ±8 kV air discharge
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Electromagnetic fieldsEN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Fast transients (burst)EN 61000-4-4/IEC 61000-4-4 Criterion A, all interfaces ±1 kVCriterion B, all interfaces ±2 kV
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Transient overvoltage (surge)EN 61000-4-5/IEC 61000-4-5 Criterion B, supply lines DC: 0.5 kV/0.5 kV (symmetrical/asymmetrical), fieldbus cable shield 1 kV
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Conducted interferenceEN 61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V
Noise emission test in accordance with EN 61000-6-4/IEC 61000-6-4 EN 55011 Class A |
| Mounting type | DIN rail mounting |
Specifications may be subject to change without notice