Product Model
IBS RL 24 DIO 8/8/8-LK

Key Features
- 1Rugged Metal Housing: IP67 protection ensures durability in harsh conditions.
- 2Comprehensive Diagnostic Functions: Advanced diagnostics for maximum system availability.
- 3Fiber Optic Technology: 500 kbaud transmission speed with polymer fiber (980/1000 µm).
- 4Digital I/O Capabilities: Eight inputs (24 V DC) and eight outputs (24 V DC, 0.5 A).
- 5Sensor/Actuator Connection: Via 5-pos. M12 female connectors for easy integration.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Width | 179 mm | Height | 67 mm |
| Depth | 71 mm | Note on dimensions | with bus connection plugs and mounting panel |
| Connection method | Optic fiber (polymer fiber 980/1000 µm) | Transmission speed | 500 kbps |
| Transmission physics | FO | Input name | Digital inputs |
| Number of inputs | 8 | Connection technology | 2-, 3-, 4-conductor |
| Input voltage range "0" signal | 0 V DC ... 5 V DC | Input voltage range "1" signal | 11 V DC ... 30 V DC |
| Typical input current per channel | 3 mA | Delay at signal change from 0 to 1 | 3 ms |
| Delay at signal change from 1 to 0 | 3 ms | Protective circuit | Electronic short-circuit/overload protection for each group |
| Output name | Digital outputs | Connection technology | 2-, 3-conductor |
| Number of outputs | 8 | Protective circuit | Electronic short-circuit/overload protection for each channel |
| Output voltage | 24 V | Maximum output current per group | 2 A |
| Maximum output current per channel | 500 mA | Nominal output voltage | 24 V |
| Output voltage when switched off | max. 1 V | Output current when switched off | max. 100 µA |
| Nominal load, inductive | 12 VA (1.2 H, 48 Ω) | Nominal load, lamp | 12 W |
| Nominal load, ohmic | 12 W | Maximum operating frequency with ohmic nominal load | max. 300 Hz |
| Behavior with overload | Auto restart | Behavior with inductive overload | Output can be destroyed |
| Overcurrent shut-down | min. 0.7 A | Output current with ground connection interrupt when switched off | max. 25 mA |
| Product type | I/O component | Product family | Ruggedline |
| Type | Block design | No. of channels | 16 |
| Supply voltage | 24 V DC | Supply voltage range | 18.5 V DC ... 32 V DC (including ripple) |
| Supply current | typ. 120 mA (plus sensor current) | Ripple | Max 3.6 V |
| Test voltage: Between bus logic and outputs | 500 V AC, 50 Hz, 1 min | Connection method | M12 connector |
| Ambient temperature (operation) | 0 °C ... 55 °C | Degree of protection | IP65/IP67 |
| Note | Seal unused slots/connections to ensure the degree of protection. | Air pressure (operation) | 860 hPa ... 1080 hPa (up to 1500 m above sea level) |
| Air pressure (storage/transport) | 660 hPa ... 1080 hPa (up to 3500 m above sea level) | Ambient temperature (storage/transport) | -25 °C ... 70 °C |
| Permissible humidity (operation) | 100 % | Permissible humidity (storage/transport) | 95 % (non-condensing) |
| Mounting type | Wall mounting |
Specifications may be subject to change without notice