- 1Dual Input Capability: Supports 2 differential inputs for thermocouples or linear voltage.
- 2Extreme Conditions: Designed for use under extreme ambient conditions, with an operating temperature range of -40 °C to +70 °C.
- 3Parameterized Channels: Channels are parameterized independently via the bus system, allowing for customizable temperature measurement.
- 4Internal Cold Junction Compensation: Internal detection and compensation of cold junction temperature, which can be parameterized.
- 5High Resolution Measurement: Measures temperature values with 16-bit resolution, ensuring high precision in temperature data acquisition.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Width | 12.2 mm | Height | 136.8 mm |
| Depth | 71.5 mm | Note on dimensions | Housing dimensions |
| Note on application | Only for industrial use | Number of interfaces | 2 |
| Connection method | Inline data jumper | Transmission speed | 500 kbps |
| ID code (dec.) | 127 | ID code (hex) | 7F |
| Length code (hex) | 02 | Length code (dec) | 02 |
| Process data channel | 32 bit | Input address area | 4 Byte |
| Output address area | 4 Byte | Register length | 32 bit |
| Required parameter data | 6 Byte | Required configuration data | 4 Byte |
| Input name | Analog UTH inputs | Description of the input | Inputs for thermocouples or linear voltage |
| Number of inputs | 2 (Thermocouples or linear voltage) | Connection method | Inline connector |
| Connection technology | 2-conductor | Note regarding the connection technology | Shielded compensating line for TC with encapsulated sensors |
| A/D conversion time | typ. 120 µs (per channel) | Sensor types that can be used (TC) | U, T, L, J, E, K, N, S, R, B, C, W, HK |
| Measuring principle | Successive approximation | Measured value representation | 16 bits (15 bits + sign bit) |
| Process data update | max. 30 ms (For both channels) | Protective circuit | Surge protection (TC channels); up to ±40 V |
| Product type | I/O component | Product family | Inline |
| Type | modular | Scope of delivery | including Inline connector and labeling field |
| Operating mode | Process data operation with 2 words | Special properties | Extreme conditions version |
| Diagnostics messages | Failure of the internal I/O supply I/O error message sent to the bus coupler
Failure of or insufficient communications power U
I/O error Error message in the process data
User error Error message in the process data | Article revision | 02 |
| Overvoltage category | II (IEC 60664-1, EN 60664-1) | Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
| Supply voltage | 7.5 V DC (via voltage jumper) | Current draw | max. 60 mA
typ. 43 mA |
| Supply voltage | 24 V DC (via voltage jumper) | Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current draw | max. 18 mA
typ. 11 mA | Test voltage: 7.5 V supply (bus logics)/24 V analog supply (analog I/O) | 500 V AC, 50 Hz, 1 min |
| Test voltage: 7.5 V supply (bus logic)/functional ground | 500 V AC, 50 Hz, 1 min | Test voltage: 24 V analog supply (analog I/O)/functional ground | 500 V AC, 50 Hz, 1 min |
| Connection name | Inline connector | Connection method | Spring-cage connection |
| Conductor cross section rigid | 0.08 mm² ... 1.5 mm² | Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 | Stripping length | 8 mm |
| Connection method | Spring-cage connection | Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
| Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² | Conductor cross section AWG | 28 ... 16 |
| Stripping length | 8 mm | Ambient temperature (operation) | -25 °C ... 55 °C (Standard)
-40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.) |
| Degree of protection | IP20 | Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) | Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) | Mounting type | DIN rail mounting |