Product Model
IB IL 24 DO2-2A-2MBD

Key Features
- 1The IB IL 24 DO 2-2A-2MBD offers two digital outputs, each capable of handling 2 A of current.
- 2Supports connection of actuators in 2-, 3-, and 4-wire technology for versatile application.
- 3Equipped with short-circuit and overload protection for reliable operation.
- 4Includes diagnostic and status indicators for easy monitoring and troubleshooting.
- 5Measures 12.2 mm in width, 119.5 mm in height, and 71.5 mm in depth, making it compact and space-efficient.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Width | 12.2 mm | Height | 119.8 mm |
| Depth | 71.5 mm | Note on dimensions | Housing dimensions |
| EMC note | EMC: class A product, see manufacturer's declaration in the download area | Color | green |
| Connection method | Inline data jumper | Transmission speed | 2 Mbps |
| ID code (dec.) | 189 | ID code (hex) | BD |
| Length code (hex) | C2 | Length code (dec) | 194 |
| Process data channel | 2 bit | Input address area | 0 Byte |
| Output address area | 2 bit | Register length | 2 bit |
| Output name | Digital outputs | Connection method | Spring-cage connection |
| Connection technology | 2-, 3-, 4-conductor | Number of outputs | 2 |
| Protective circuit | Overload protection, short-circuit protection of outputs | Output voltage | 24 V DC (via voltage jumper) |
| Maximum output current per channel | 2 A | Maximum output current per module | 4 A |
| Nominal output voltage | 24 V DC (voltage difference at I | Nominal load, inductive | 48 W |
| Nominal load, lamp | 48 W | Nominal load, ohmic | 48 VA |
| Behavior with overload | Auto restart | Behavior with inductive overload | Output can be destroyed |
| Behavior at voltage switch-off | The output follows the power supply without delay | Product type | I/O component |
| Product family | Inline | Type | modular
Inline |
| No. of channels | 2 | Diagnostics messages | Short-circuit or overload of the digital outputs Error message in the diagnostic code (bus) and display (2 Hz) via the LED (D) on the module |
| Supply voltage | 7.5 V DC (via voltage jumper) | Current draw | max. 60 mA |
| Supply voltage | 24 V DC (via voltage jumper) | Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current draw | max. 4 A | Test voltage: 5 V supply, incoming remote bus/7.5 V supply (bus logics) | 500 V AC, 50 Hz, 1 min |
| Test voltage: 5 V supply, outgoing remote bus/7.5 V supply (bus logics) | 500 V AC, 50 Hz, 1 min | Test voltage: 7.5 V supply (bus logics)/24 V supply (I/O) | 500 V AC, 50 Hz, 1 min |
| Test voltage: 24 V supply (I/O) / functional ground | 500 V AC, 50 Hz, 1 min | Connection name | Inline connector |
| Connection method | Spring-cage connection | Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.08 mm² ... 1.5 mm² | Conductor cross section AWG | 28 ... 16 |
| Stripping length | 8 mm | Connection method | Spring-cage connection |
| Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² | Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 | Stripping length | 8 mm |
| Ambient temperature (operation) | -25 °C ... 55 °C | Degree of protection | IP20 |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Ambient temperature (storage/transport) | -25 °C ... 85 °C | Permissible humidity (operation) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Permissible humidity (storage/transport) | 10 % ... 95 % (according to DIN EN 61131-2) | Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
| Mounting type | DIN rail mounting |
Specifications may be subject to change without notice