Product Model
IB IL 24 DI16-2MBD-PAC/SN

Key Features
- 116 Digital Inputs: Connect up to 16 digital sensors for comprehensive signal acquisition.
- 22-Wire/3-Wire Connectivity: Flexibility in connecting sensors with both 2 and 3-wire technology.
- 3Diagnostic Indicators: Monitor status and diagnose issues with built-in diagnostic indicators.
- 4High-Speed Transmission: Fast data transmission at 2 Mbps for efficient communication.
- 5IP20 Protection: Ensured safety with IP20 degree of protection against solid objects and water.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Width | 48.8 mm | Height | 140.5 mm |
| Depth | 71.5 mm | Note on dimensions | Housing dimensions |
| Color | green | Connection method | Inline data jumper |
| Transmission speed | 2 Mbps | ID code (dec.) | 190 |
| ID code (hex) | BE | Length code (hex) | 01 |
| Length code (dec) | 01 | Process data channel | 16 bit |
| Input address area | 2 Byte | Output address area | 0 Byte |
| Register length | 16 bit | Required parameter data | 1 Byte |
| Required configuration data | 4 Byte | Input name | Digital inputs |
| Description of the input | EN 61131-2 type 1 | Number of inputs | 16 |
| Connection method | Spring-cage connection | Connection technology | 3-conductor |
| Input voltage | 24 V DC | Input voltage range "0" signal | -3 V DC ... 5 V DC |
| Input voltage range "1" signal | 15 V DC ... 30 V DC | Nominal input voltage U | 24 V DC |
| Nominal input current at U | min. 3 mA (at nominal voltage) | Typical response time | < 1 ms |
| Protective circuit | Short-circuit and overload protection | Product type | I/O component |
| Product family | Inline | Type | modular
Inline |
| Scope of delivery | including Inline connectors and marking fields, connectors numbered individually | No. of channels | 16 |
| Operating mode | Process data mode with one word | Article revision | 05 |
| Maximum power dissipation for nominal condition | 14.5 W | Supply voltage | 7.5 V DC (via voltage jumper) |
| Current draw | max. 80 mA | Power consumption | max. 0.6 W |
| Supply voltage | 24 V DC (via voltage jumper) | Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current draw | max. 4 A | Test voltage: 5 V supply, incoming remote bus/7.5 V supply (bus logics) | 500 V AC, 50 Hz, 1 min |
| Test voltage: 5 V supply, outgoing remote bus/7.5 V supply (bus logics) | 500 V AC, 50 Hz, 1 min | Test voltage: 7.5 V supply (bus logics)/24 V supply (I/O) | 500 V AC, 50 Hz, 1 min |
| Test voltage: 24 V supply (I/O) / functional ground | 500 V AC, 50 Hz, 1 min | Connection name | Inline connector |
| Connection method | Spring-cage connection | Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.08 mm² ... 1.5 mm² | Conductor cross section AWG | 28 ... 16 |
| Stripping length | 8 mm | Connection method | Spring-cage connection |
| Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² | Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 | Stripping length | 8 mm |
| Degree of protection | IP20 | Ambient temperature (operation) | -25 °C ... 55 °C |
| Degree of protection | IP20 | Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % (according to DIN EN 61131-2) | Permissible humidity (storage/transport) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) | Mounting type | DIN rail mounting |
Specifications may be subject to change without notice