Product Model
FLM DIO 8/4 M8

Key Features
- 1Compact dimensions for easy installation in close proximity to the process.
- 2Channel-specific diagnostics for reliable operation and quick troubleshooting.
- 3500 mA maximum current per digital I/O for demanding applications.
- 4Built-in protection to ensure device safety and longevity.
- 5Consistent and reliable connection via M8 connectors for easy integration.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Width | 29.8 mm | Height | 143 mm |
| Depth | 26.5 mm | Drill hole spacing | 133 mm |
| Note on dimensions | Length details incl. fixing clips | Color | black |
| Connection method | M8 connector | Designation connection point | Copper cable |
| Number of positions | 4 | Transmission speed | 500 kbps |
| ID code (dec.) | 179 | ID code (hex) | B3 |
| Length code (hex) | 81 | Length code (dec) | 129 |
| Process data channel | 8 bit | Input address area | 8 bit |
| Output address area | 8 bit | Register length | 8 bit |
| Required parameter data | 3 Byte | Required configuration data | 5 Byte |
| Input name | Digital inputs | Description of the input | IEC 61131-2 type 1 |
| Number of inputs | 8 (4 fixed, 4 freely selectable) | Connection method | M8 connector |
| Connection technology | 2-, 3-conductor | Input voltage | 24 V DC |
| Input voltage range "0" signal | -30 V DC ... 5 V DC | Input voltage range "1" signal | 13 V DC ... 30 V DC |
| Nominal input voltage U | 24 V DC | Filter time | 3 ms |
| Protective circuit | Reverse polarity protection | Output name | Digital outputs |
| Connection method | M8 connector | Connection technology | 2-, 3-conductor |
| Number of outputs | 4 (Can also be used as an input) | Protective circuit | Short-circuit protection |
| Output voltage | 24 V DC | Maximum output current per channel | 500 mA |
| Product type | I/O component | Product family | Fieldline |
| Type | modular | No. of channels | 8 |
| Voltage supply U | 24 V DC | Connection method | M8 connector |
| Designation | U | Number of positions | 4 |
| Supply voltage | 24 V DC | Supply voltage range | 18 V DC ... 30 V DC (including ripple) |
| Supply current | 3 A | Test voltage: To I/O | 500 V AC |
| Connection method | M8 connector | Ambient temperature (operation) | -25 °C ... 60 °C |
| Degree of protection | IP65/IP67 | Air pressure (operation) | 80 kPa ... 106 kPa (up to 2000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % | Permissible humidity (storage/transport) | 10 % ... 95 % |
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) | Mounting type | Wall mounting |
Specifications may be subject to change without notice