Product Model
FLKM 50-PA-S300/6J/SMKDS1

Key Features
- 1Connects up to 32 channels for seamless industrial automation.
- 2Separate voltage supply via angled miniature PCB terminal blocks.
- 3Suitable for Siemens SIMATIC S7-300 and ET 200 M controllers.
- 4Rated surge voltage of 0.6 kV (1.2/50 μs) for enhanced reliability.
- 5Non-isolated digital I/O cards with nominal voltage < 50 V AC, 60 V DC Max.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Product type | Front adapter | Insulation | Functional insulation |
| Overvoltage category | II | Pollution degree | 2 |
| Operating voltage (AC) | ≤ 25 V AC | Operating voltage (DC) | ≤ 60 V DC |
| Current (Per path) | ≤ 1 A | Current (per connection) | ≤ 8 A (Feed-in via separate power supply) |
| Current (Total current per byte) | ≤ 2 A (Feed-in via connector) | Rated insulation voltage | 63 V |
| Rated surge voltage | 0.6 kV (1.2/50 μs) | Suitable I/O card | CPU 313C
CPU 313C-2DP
CPU 313C-2PtP
CPU 314C-2DP
CPU 314C-2PtP
6ES7321-1BL00-0AA0
6ES7322-1BL00-0AA0
6ES7323-1BL00-0AA0
6ES7331-1KF01-0AB0
6ES7331-7NF00-0AB0
6ES7331-7NF10-0AB0
6ES7331-7PF01-0AB0
6ES7331-7PF11-0AB0
6ES7332-5HF00-0AB0
6ES7350-2AH01-0AE0
6ES7357-4AH01-0AE0 |
| Connection method | IDC/FLK pin strip | Number of connections | 1 |
| Number of positions | 50 | Pitch | 2.54 mm |
| Connection method | Screw connection | Conductor cross section rigid | 0.14 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² | Conductor cross section AWG | 26 ... 16 |
| Width | 115 mm | Height | 21.3 mm |
| Degree of protection | IP00 | Degree of protection (Installation location) | ≥ IP54 (Installation location) |
| Ambient temperature (operation) | -20 °C ... 50 °C | Altitude | ≤ 2000 m |
| Standards/regulations | DIN EN 50178: 1998-04 | Standard designation | Air clearances and creepage distances |
| Mounting position | any | Notes on operation | For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met. |
Specifications may be subject to change without notice