Product Model
FLKM 14/8P/HF/PLC

Key Features
- 1Ensures safe and durable operation in various environments.
- 2Easy installation on standard DIN rails for efficient setup.
- 3Supports operating voltages up to 30 V AC and 60 V DC.
- 4Meets overvoltage category II and pollution degree 2 standards.
- 5Ideal for PLC systems with 8 channels and additional terminal blocks per signal.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Product type | Interface module | Product family | VARIOFACE |
| Article revision | 06 | Insulation | Functional insulation |
| Overvoltage category | II | Pollution degree | 2 |
| Operating voltage (AC) | ≤ 30 V AC | Operating voltage (DC) | ≤ 60 V DC |
| Current (per branch) | ≤ 1 A | Current (Voltage supply) | ≤ 3 A |
| Rated insulation voltage | 63 V | Rated surge voltage | 0.6 kV (1.2/50 μs) |
| Connection in acc. with standard | IEC 60603-13 | Connection method | FLK14 pin strip |
| Number of connections | 1 | Number of positions | 14 |
| Insertion/withdrawal cycles | > 50 | Pitch | 2.54 mm |
| Connection method | Screw connection | Stripping length | 7 mm |
| Screw thread | M3 | Number of positions | 20 |
| Conductor cross section rigid | 0.2 mm² ... 4 mm² | Conductor cross-section rigid (2 conductors with same cross section) | 0.2 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm²
0.25 mm² ... 1.5 mm² (Ferrule without plastic sleeve)
0.25 mm² ... 2.5 mm² (Ferrule with plastic sleeve) | Conductor cross section flexible (2 conductors with same cross section) | 0.2 mm² ... 1.5 mm²
0.25 mm² ... 0.75 mm² (Ferrule without plastic sleeve)
0.5 mm² ... 0.5 mm² (TWIN ferrule with plastic sleeve) |
| Conductor cross section AWG | 24 ... 12 | Tightening torque | 0.5 Nm ... 0.6 Nm |
| Pitch | 5.08 mm | Width | 56.25 mm |
| Height | 77 mm | Depth | 57.17 mm |
| Degree of protection (Module) | IP00 | Degree of protection (Installation location) | ≥ IP54 |
| Ambient temperature (operation) | -20 °C ... 50 °C | Ambient temperature (storage/transport) | -20 °C ... 70 °C |
| Altitude | ≤ 2000 m | Standards/regulations | EN IEC 60664-1 |
| Mounting type | DIN rail mounting | Mounting position | any |
| Notes on operation | For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met. |
Specifications may be subject to change without notice