Product Model
ELR H5-I-SC- 24DC/500AC-0,6-SP

Key Features
- 1Space-saving design: 22.5 mm wide for compact installations.
- 2Long service life: Designed for extended operational periods.
- 3Adjustable overload shutdown: Ensures motor safety and reliability.
- 4Surge protection: Safeguards against electrical surges and spikes.
- 5DIN rail mounting: Easy installation on vertical or horizontal DIN rails.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Product type | Hybrid motor starters | Product family | CONTACTRON |
| Operating mode | 100% operating factor | Insulation | safe isolation |
| Overvoltage category | III | Pollution degree | 2 |
| Number of phases | 3 | Service life electrical | 3x 10 |
| Maximum power dissipation for nominal condition | 1.5 W | Reversing frequency | ≤ 2 Hz |
| Maximum power dissipation | 1.5 W | Minimum power dissipation | 1.1 W |
| Coordination type | 1 | Rated insulation voltage | 500 V |
| Rated surge voltage | 6 kV | Rated control circuit supply voltage U | 24 V DC |
| Control supply voltage range | 19.2 V DC ... 30 V DC | Rated control supply current I | 40 mA |
| Protective circuit | Surge protection
Reverse polarity protection | Rated actuating voltage U | 24 V DC |
| Triggering voltage range | 19.2 V DC ... 30 V DC | Rated actuating current I | 5 mA (Input type 1) |
| Switching threshold | 9.6 V (“0” signal)
19.2 V (“1” signal) | Typical turn-off time | < 30 ms |
| Rated operating voltage U | 500 V AC | Operating voltage range | 42 V AC ... 550 V AC |
| Rated operating current I | 0.6 A (AC-51)
0.6 A (AC-53a) | Mains frequency | 50/60 Hz |
| Load current range | 75 mA ... 600 mA (see to derating) | Trigger characteristic in acc. with IEC 60947-4-2 | Class 10A |
| Cooling time | 20 min (for auto reset) | Leakage current | 0 mA |
| Residual voltage | < 0.2 V | Protective circuit | Surge protection |
| Note | Confirmation: floating change-over contact, signal contact | Contact switching type | 1 changeover contact |
| Connection method | Screw connection | Stripping length | 8 mm |
| Screw thread | M3 | Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² | Conductor cross section AWG | 24 ... 14 |
| Connection method | Screw connection | Stripping length | 8 mm |
| Screw thread | M3 | Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² | Conductor cross section AWG | 24 ... 14 |
| Status display | LED (yellow) | Operating voltage display | Green LED |
| Error indication | Red LED | Width | 22.5 mm |
| Height | 107 mm | Depth | 114 mm |
| Flammability rating according to UL 94 | V0 (Housing) | Degree of protection | IP20 |
| Ambient temperature (operation) | -25 °C ... 70 °C | Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Certificate | NLDX.E228652 | SCCR | 100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault)))
5 kA (480 V AC (fuse: 20 A RK5 (standard fault))) |
| FLA | 0.6 A (480 V) | Standards/regulations | DIN EN 50178 |
| Standards/regulations | IEC 60947-4-2 | Mounting type | DIN rail mounting |
| Assembly note | can be aligned with spacing: see derating | Mounting position | Vertical (horizontal DIN rail) |
Specifications may be subject to change without notice