Product Model
XT2V 160 Ekip Dip LIG In=10A 4p F F

Key Features
- 1Designed with solid-state release for consistent performance.
- 2Measuring 120 mm in width and 82.5 mm in height.
- 3Meets IEC standards for safety and efficiency.
- 4Suitable for various AC power distribution needs.
- 5Withstands 240 cycles per hour and 25,000 cycles mechanically.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK108467A6707 | Product Net Width | 120 mm |
| Product Net Height | 130 mm | Product Net Depth / Length | 82.5 mm |
| Product Net Weight | 1.3 kg | Circuit Breaker Type to be Associated | Power Distribution |
| Product Main Type | SACE Tmax XT | Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker | Version | F |
| CAD Dimensional Drawing | 1SDH002230A1002 | Current Type | AC |
| Electrical Durability | 120 cycles per hour 8000 cycle | Mechanical Durability | 240 cycles per hour 25000 cycle |
| Number of Poles | 4P | Order Multiple | 1 piece |
| Power Loss | at Rated Operating Conditions per Pole 0.1 W | Rated Current (In) | 10 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC 500 V DC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 200 kA (230 V AC) 200 kA (240 V AC) 200 kA (380 V AC) 150 kA (415 V AC) 150 kA (440 V AC) 150 kA (500 V AC) 70 kA (525 V AC) 50 kA (690 V AC) 15 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 200 kA (230 V AC) 200 kA (240 V AC) 200 kA (380 V AC) 150 kA (415 V AC) 150 kA (440 V AC) 150 kA (500 V AC) 70 kA (525 V AC) 50 kA (690 V AC) 20 kA | Rated Uninterrupted Current (Iu) | 160 A |
| Release | Ekip Dip LIG | Release Type | EL |
| Short-Circuit Performance Level | V | Standards | IEC60947-2 |
| Sub-type | XT2 | Terminal Connection Type | Front |
| ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA101953R1 |
Specifications may be subject to change without notice