Product Model
XT2N 160 Ekip Dip LSIG In=100A 3p F F

Key Features
- 1Designed to withstand 8000 cycles, ensuring long-lasting performance.
- 2Advanced technology for quick and reliable circuit breaking.
- 3Suitable for various electrical applications requiring four poles.
- 4Measures 120 mm x 130 mm x 82.5 mm, ideal for space-efficient installations.
- 5Meets IEC standards, ensuring compliance with international safety regulations.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Product Net Width | 90 mm | Product Net Height | 130 mm |
| Product Net Depth / Length | 82.5 mm | Product Net Weight | 1.2 kg |
| Circuit Breaker Type to be Associated | Power Distribution | Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
| Version | F | CAD Dimensional Drawing | 1SDH002230A1001 |
| Current Type | AC | Electrical Durability | 120 cycles per hour 8000 cycle |
| Mechanical Durability | 240 cycles per hour 25000 cycle | Number of Poles | 3P |
| Power Loss | at Rated Operating Conditions per Pole 4.20 W | Rated Current (In) | 100 A |
| Rated Frequency (f) | 50/60 Hz | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V AC | Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA |
| Rated Uninterrupted Current (Iu) | 160 A | Rated Voltage (Ur) | 690 V AC |
| Release | Ekip Dip LSIG | Release Type | EL |
| Short-Circuit Performance Level | N | Standards | IEC |
| Sub-type | XT2 | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| Manufacturer ID | 1SDA100008R1 |
Specifications may be subject to change without notice