Product Model
T6N 800 BREAKING PART 4p F F

Key Features
- 1High Electrical Durability: 5000 cycles at 60 cycles per hour.
- 2Robust Design: Front terminal connection with thermal-magnetic release.
- 3Compliance with IEC Standards: Meets rigorous IEC standards for safety and performance.
- 4High Short-Circuit Breaking Capacity: 36 kA at various voltage levels.
- 5Reliable Operation: Suitable for main circuit applications up to 800 A.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK10103A1058 9AKK108467A6707 | Product Net Width | 280 mm |
| Product Net Height | 268 mm | Product Net Depth / Length | 103.5 mm |
| Product Net Weight | 10.5 kg | Product Main Type | SACE Tmax T |
| Product Name | Moulded Case Circuit Breaker | Product Type | Breaking Part |
| Suitable For | T6 | Suitable for Product Class | Moulded Case Circuit Breakers |
| Version | F | Electrical Durability | 5000 cycle 60 cycles per hour |
| Mechanical Durability | 20000 cycle 120 cycles per hour | Number of Poles | 4 |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC 750 V DC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 70 kA (230 V AC) 70 kA (380 V AC) 36 kA (400 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 30 kA (500 V AC) 25 kA (690 V AC) 15 kA |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 10 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 70 kA (230 V AC) 70 kA (380 V AC) 36 kA (400 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 30 kA (500 V AC) 25 kA (690 V AC) 20 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 2 Poles in Series 25 kA (750 V DC) 3 Poles in Series 16 kA |
| Rated Uninterrupted Current (Iu) | 800 A | Short-Circuit Performance Level | N |
| Standards | IEC | Sub-type | T6 |
| Terminal Connection Type | Fixed Circuit-Breakers Front | Test Voltage Max (Utest) | 3500 V |
| ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q | UNSPSC | 39121100 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | eClass | V11.1 : 27370409 |
| Manufacturer ID | 1SDA060339R1 |
Specifications may be subject to change without notice