Product Model
T6L 800 PR221DS-I In=800 4p F F

Key Features
- 1High-performance circuit breaker with solid-state release.
- 2Rated for 800 A and 1000 V AC.
- 3Four poles for enhanced protection and control.
- 4Front terminals for easy installation and maintenance.
- 5Meets IEC standards for reliability and safety.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK10103A1058 9AKK108467A6707 | Product Net Width | 280 mm |
| Product Net Height | 268 mm | Product Net Depth / Length | 103.5 mm |
| Product Net Weight | 12 kg | Product Main Type | SACE Tmax T |
| Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
| Suitable For | T6 | Suitable for Product Class | Moulded Case Circuit Breakers |
| Version | F | Electrical Durability | 5000 cycle 60 cycles per hour |
| Mechanical Durability | 20000 cycle 120 cycles per hour | Number of Poles | 4 |
| Power Loss | at Rated Operating Conditions per Pole 32 W | Rated Current (In) | 800 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 150 kA (230 V AC) 150 kA (380 V AC) 75 kA (400 V AC) 75 kA (415 V AC) 75 kA (440 V AC) 60 kA (500 V AC) 49 kA (690 V AC) 22.5 kA |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 10 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 100 kA (400 V AC) 100 kA (415 V AC) 100 kA (440 V AC) 80 kA (500 V AC) 65 kA (690 V AC) 30 kA |
| Rated Uninterrupted Current (Iu) | 800 A | Release | PR221DS-I |
| Release Type | EL | Short-Circuit Performance Level | L |
| Standards | IEC | Sub-type | T6 |
| Terminal Connection Type | Fixed Circuit-Breakers Front | Test Voltage Max (Utest) | 3500 V |
| ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q | UNSPSC | 39121100 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | eClass | V11.1 : 27370409 |
| Manufacturer ID | 1SDA060306R1 |
Specifications may be subject to change without notice