Product Model
OTM40F3M230V

Key Features
- 1High Thermal Current: Handles up to 40 A in both free-air and fully enclosed conditions.
- 2Robust Insulation: Meets IEC/EN 60664-1 standards with a rated insulation voltage of 750 V.
- 3Compact Design: Base-mounted with a small footprint, suitable for various industrial settings.
- 4Manual Operation: Equipped with a handle for manual operation in emergency situations.
- 5Comprehensive Safety Features: Includes protected clamp terminals and meets EU RoHS and CE standards.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Degree of Protection | Front IP20 | Pollution Degree | 3 |
| Product Net Width | 160 mm | Product Net Height | 100 mm |
| Product Net Depth / Length | 116 mm | Product Net Weight | 0.9 kg |
| Cable Cross-Section | Cu 0.75 ... 10 mm² | Conventional Free-air Thermal Current (Ith) | Π= 40 °C 40 A |
| Conventional Thermal Current (Ithe) | Fully Enclosed 40 A | Degree of Protection | Front IP20 |
| Distance Between Phases | Standard | Handle Color | Black |
| Handle Type | Direct mounted handle | Lock Type | Yes |
| Mechanical Durability | 20000 | Motor Operational Voltage | 110 ... 240 V AC/DC |
| Mounting Type | Base mounting | Number of Poles | 3P |
| Operating Mode | Front operated | Pollution Degree | 3 |
| Position of Line Terminals | Top In - Bottom Out | Power Loss | at Rated Operating Conditions per Pole 1.6 W |
| Rated Conditional Short-Circuit Current (Inc) | (125 A fuse, 415 V) 50 kA (125 A fuse, 690 V) 18 kA (63 A fuse, 690 V) 50 kA | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 750 V | Rated Operational Current AC-21A (Ie) | (380 ... 415 V) 40 A (500 V) 40 A (690 V) 40 A |
| Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 40 A (500 V) 40 A (690 V) 40 A | Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 23 A (500 V) 23 A (690 V) 12 A |
| Rated Operational Power AC-23A (Pe) | (220 ... 240 V) 5.5 kW (400 ... 415 V) 11 kW (500 V) 11 kW (690 V) 11 kW | Rated Operational Voltage | Main Circuit 750 V |
| Rated Short-Circuit Making Capacity (Icm) | (690 V) 0.71 kA | Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 0.5 kA |
| Special Functions | No | Standards | IEC 60947-3 |
| Switches Operating Mechanism | Mechanism at the End of the Switch | Terminal Type | Screw Terminals |
| Tightening Torque | acc. IEC 60947-1 0.8 N·m | Tightening Torque | acc. IEC 60947-1 0.8 N·m |
| Object Classification Code | Q | ETIM 8 | EC000216 - Switch disconnector |
| ETIM 9 | EC000216 - Switch disconnector (low voltage) | UNSPSC | 39122233 |
| IDEA Granular Category Code (IGCC) | 5290 >> Disconnect switch | eClass | V11.1 : 27371403 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | Manufacturer ID | 1SCA122972R1001 |
Specifications may be subject to change without notice