Product Model
OT800U03

Key Features
- 1High Amperage Rating: 800 A for reliable power disconnection.
- 2Finger-Proof Construction: Dead front design and terminal shrouds reduce the risk of live part contact.
- 3Modular Design: Easy to install and maintain with a modular construction.
- 4Superior Short-Circuit Protection: 110 kA short circuit current rating ensures safe operation.
- 5Front Operated Mechanism: Clear position indication and quick make, quick brake mechanism for easy operation.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Degree of Protection | Front IP00 | Environmental Information | 1SCC301233D0201 |
| Pollution Degree | 3 | Product Net Width | 334.5 mm |
| Product Net Height | 372 mm | Product Net Depth / Length | 151.5 mm |
| Product Net Weight | 17.2 kg | Conventional Thermal Current (Ithe) | Fully Enclosed 800 A |
| Degree of Protection | Front IP00 | Distance Between Phases | Standard |
| Handle Type | Handle and shaft not included | Lock Type | No |
| Mechanical Durability | 6000 | Mounting Type | Base mounting |
| Number of Poles | 3P | Operating Mode | Front operated |
| Pollution Degree | 3 | Position of Line Terminals | Top In - Bottom Out Bottom In - Top Out |
| Power Loss | at Rated Operating Conditions per Pole 29 W | Rated Impulse Withstand Voltage (Uimp) | 12 kV |
| Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 1000 V | Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 1600 A (500 V) 1600 A (690 V) 1600 A |
| Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 1250 A (500 V) 1250 A (690 V) 1250 A | Rated Operational Power AC-23A (Pe) | (380 ... 415 V) 710 kW (500 V) 900 kW (690 V) 1200 kW |
| Rated Operational Voltage | Main Circuit 1000 V | Rated Short-Circuit Making Capacity (Icm) | (690 V) 110 kA |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 50 kA | Special Functions | No |
| Standards | IEC 60947-3 / UL 98 / CSA C22.2 NO.4 | Switches Operating Mechanism | Mechanism at the End of the Switch 03 (Left Side) |
| Terminal Type | Lug terminals | Tightening Torque | acc. IEC 60947-1 56.5 N·m |
| Maximum Operating Voltage UL/CSA | 600 V | Ampere Rating | 800 A |
| Horsepower Rating UL/CSA | (acc. to UL 240 V) 250 Hp (acc. to UL 480 V) 500 Hp (acc. to UL 600 V) 500 Hp | Tightening Torque | acc. IEC 60947-1 56.5 N·m |
| Tightening Torque UL/CSA | 500 in·lb | Object Classification Code | Q |
| ETIM 8 | EC000216 - Switch disconnector | ETIM 9 | EC000216 - Switch disconnector (low voltage) |
| UNSPSC | 39122233 | IDEA Granular Category Code (IGCC) | 5290 >> Disconnect switch |
| eClass | V11.1 : 27371403 | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| E-Number (Finland) | 3642441 | Manufacturer ID | 1SCA105635R1001 |
Specifications may be subject to change without notice