Product Model
OT400E12CP

Key Features
- 1High Performance: Handles currents from 16 A to 3200 A, ensuring reliable operation in various applications.
- 2Easy Installation: Manually controlled with a simple handle operation, making it easy to install and use.
- 3Robust Design: Constructed with a black plastic IP65 handle and shaft, providing protection against environmental factors.
- 4Secure Operation: Features a padlockable handle in the OFF-position and door interlock in the ON-position for enhanced security.
- 5Compliance: Meets EU Directive 2011/65/EU and Amendment 2015/863, ensuring RoHS compliance and environmental safety.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Degree of Protection | Front IP20 | Environmental Information | 1SCC303050D0201 |
| Pollution Degree | 3 | Product Net Width | 221 mm 8.7 in |
| Product Net Height | 185 mm 7.28 in | Product Net Depth / Length | 203 mm 7.99 in |
| Product Net Weight | 6 kg 13.23 lb | Conventional Free-air Thermal Current (Ith) | Π= 40 °C 400 A |
| Conventional Thermal Current (Ithe) | Fully Enclosed 400 A | Degree of Protection | Front IP20 |
| Distance Between Phases | Standard | Handle Color | Black |
| Handle Type | Handle and shaft included | Mounting Type | Base mounting |
| Number of Poles | 3P | Operating Mode | Front operated |
| Pollution Degree | 3 | Position of Line Terminals | Top In - Bottom Out, Bottom In - Top Out |
| Power Loss | at Rated Operating Conditions per Pole 10 W | Rated Impulse Withstand Voltage (Uimp) | 12 kV |
| Rated Insulation Voltage (Ui) | 1000 V | Rated Operational Current AC-21A (Ie) | (380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A |
| Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A | Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A |
| Rated Operational Current AC-31B (Ie) | (380 ... 415 V) 400 A | Rated Operational Current AC-33B (Ie) | (380 ... 415 V) 400 A |
| Rated Operational Power AC-23A (Pe) | (380 ... 415 V) 220 kW (500 V) 280 kW (690 V) 400 kW | Rated Operational Voltage | Main Circuit 1000 V |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 15 kiloampere rms | Switches Operating Mechanism | Mechanism Between the Poles 12 (Between the Poles) |
| Terminal Type | Screw Terminals | Terminal Width | 25 mm |
| Tightening Torque | acc. IEC 60947-1 30 ... 44 N·m | Transition Type | Open |
| Ampere Rating | 400 A | Tightening Torque | acc. IEC 60947-1 30 ... 44 N·m |
| Object Classification Code | Q | ETIM 8 | EC000216 - Switch disconnector |
| ETIM 9 | EC000216 - Switch disconnector (low voltage) | eClass | V11.1 : 27371403 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | E-Number (Finland) | 3641514 |
| Manufacturer ID | 1SCA022776R9590 |
Specifications may be subject to change without notice