Product Model
OT400DFCC3T

Key Features
- 1Rigid Glass Reinforced Polycarbonate Enclosure: Durable and UV-protected for both outdoor and indoor use.
- 2IP65 Protection: Resistant to low-pressure water jets, ensuring reliable operation in harsh environments.
- 3Padlockable Handle: Secure with three padlocks, providing enhanced safety and security.
- 4Interlockable Cover: Ensures the cover is securely locked, preventing accidental operation.
- 5PE Terminals Included: Easy cable connections with included PE terminals for efficient setup.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Degree of Protection | acc. to IEC 60529 IP65 | Pollution Degree | 3 |
| Product Net Width | 380 mm | Product Net Height | 840 mm |
| Product Net Depth / Length | 180 mm | Product Net Weight | 14.206 kg |
| Cable Entry Position | Top/Bottom | Cable Outlets Per Side | II-flange / II-flange |
| Connecting Capacity Main Circuit | Hole Diameter 10 mm Screw Clamp / PE Terminal 4pc,25 ... 120 mm² | Conventional Thermal Current (Ithe) | Fully Enclosed 400 A |
| Degree of Protection | acc. to IEC 60529 IP65 | Enclosure Material | Plastic |
| Handle Color | Black | Handle Type | Pistol handle |
| Impact Resistance Rating | Housing IK08 | Maximum Mounted Auxiliary Contacts | 2 NO, 2 NC |
| Mounted Auxiliary Contacts | 2 NO, 1 NC | Neutral Type | No neutral terminal |
| Number of Auxiliary Contacts NC | 1 | Number of Auxiliary Contacts NO | 2 |
| Number of Poles | 3P | Pollution Degree | 3 |
| Position of Line Terminals | Top In - Bottom Out | Position of PE Terminals | Top In - Bottom Out |
| Power Loss | at Rated Operating Conditions per Pole 10 W | Rated Conditional Short-Circuit Current (Inc) | 61.5 kA |
| Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 1000 V | Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A |
| Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A | Rated Operational Power AC-23A (Pe) | (380 ... 415 V) 220 kW (500 V) 280 kW (690 V) 355 kW |
| Rated Operational Voltage | Main Circuit 1000 V | Rated Short-Circuit Making Capacity (Icm) | (1000 V AC) 65 kA |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 15 kA | Recommended Screw Driver | Main Circuit M10 |
| Standards | IEC 60947-1, -3 | Tightening Torque | Main Circuit 44 N·m |
| Recommended Screw Driver | Main Circuit M10 | Tightening Torque | Main Circuit 44 N·m |
| Object Classification Code | Q | ETIM 8 | EC000216 - Switch disconnector |
| ETIM 9 | EC000216 - Switch disconnector (low voltage) | UNSPSC | 39122205 |
| IDEA Granular Category Code (IGCC) | 5166 >> Safety switch | eClass | V11.1 : 27371403 |
| WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) | E-Number (Finland) | 3642416 |
| E-Number (Norway) | 1429312 | E-Number (Sweden) | 3140234 |
| Manufacturer ID | 1SCA022277R0490 |
Specifications may be subject to change without notice