Product Model
OT250KLCC3TZ

Key Features
- 1High-Rated Power Handling: Rated operation power at AC-3, 400 V: 132 kW.
- 2IP65 Protection: Degree of protection (IP) front side: IP65, ensuring protection against dust and water jets.
- 3Galvanized Steel Enclosure: Rigid glass reinforced polycarbonate enclosure with UV protection and low-pressure water jet resistance.
- 4Padlockable Handle: Handle padlockable for 3 padlocks, enhancing security during maintenance.
- 5Comprehensive Safety Features: Inbuilt gas pressure relief function to protect users in case of an internal arc, and interlock function for added safety.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Degree of Protection | acc. to IEC 60529 IP65 | Pollution Degree | 3 |
| Product Net Width | 400 mm | Product Net Height | 600 mm |
| Product Net Depth / Length | 230 mm | Product Net Weight | 19.91 kg |
| Cable Entry Position | Top/Bottom | Cable Outlets Per Side | 2xC-flange / 2xC-flange, Knock-outs: 10mm, 12.5mm, 20.5mm, 25.5mm, 32.5mm |
| Connecting Capacity Main Circuit | Hole Diameter 8 mm Screw Clamp / PE Terminal 4pc,10 ... 70+4pc M8 mm² | Conventional Thermal Current (Ithe) | Fully Enclosed 250 A |
| Degree of Protection | acc. to IEC 60529 IP65 | Enclosure Material | Steel sheet |
| Handle Color | Black | Handle Type | Pistol handle |
| Impact Resistance Rating | Housing IK09 | Maximum Mounted Auxiliary Contacts | 2 NO, 2 NC |
| Mounted Auxiliary Contacts | 2 NO, 1 NC | Neutral Type | No neutral terminal |
| Number of Auxiliary Contacts NC | 1 | Number of Auxiliary Contacts NO | 2 |
| Number of Poles | 3P | Pollution Degree | 3 |
| Position of Line Terminals | Top In - Bottom Out | Position of PE Terminals | Top In - Bottom Out |
| Power Loss | at Rated Operating Conditions per Pole 6.5 W | Rated Conditional Short-Circuit Current (Inc) | 40.5 kA |
| Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 1000 V | Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A |
| Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A | Rated Operational Power AC-23A (Pe) | (380 ... 415 V) 132 kW (500 V) 160 kW (690 V) 200 kW |
| Rated Operational Voltage | Main Circuit 1000 V | Rated Short-Circuit Making Capacity (Icm) | (1000 V AC) 30 kA |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 8 kA | Recommended Screw Driver | Main Circuit M8 |
| Standards | IEC 60947-1, -3 | Tightening Torque | Main Circuit 22 N·m |
| Recommended Screw Driver | Main Circuit M8 | Tightening Torque | Main Circuit 22 N·m |
| Object Classification Code | Q | ETIM 8 | EC000216 - Switch disconnector |
| ETIM 9 | EC000216 - Switch disconnector (low voltage) | UNSPSC | 39122205 |
| IDEA Granular Category Code (IGCC) | 5166 >> Safety switch | eClass | V11.1 : 27371403 |
| WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) | E-Number (Finland) | 3642725 |
| E-Number (Norway) | 1429108 | E-Number (Sweden) | 3140608 |
| Manufacturer ID | 1SCA022281R5690 |
Specifications may be subject to change without notice