Product Model
MS132-0.16T

Key Features
- 1Compact design with a width of 45 mm, ideal for space-constrained applications.
- 2Provides fuse-less protection against overload and short-circuit, ensuring reliable operation.
- 3Features a trip class of 10 for high reliability in critical applications.
- 4Includes a built-in disconnection function for easy manual connection and disconnection of transformers.
- 5Offers a rated service short-circuit breaking capacity of 100 kA at 400 VAC.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Product Net Width | 45 mm | Product Net Height | 90 mm |
| Product Net Depth / Length | 86.75 mm | Product Net Weight | 0.215 kg |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (230 V AC) 100 kA (400 V AC) 100 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 100 kA |
| Rated Instantaneous Short-Circuit Current Setting (Ii) | 3.2 A | Setting Range | 0.10 ... 0.16 A |
| Rated Operational Voltage | Main Circuit 690 V AC | Rated Operational Current (Ie) | 0.16 A |
| Rated Frequency (f) | Main Circuit 50 Hz Main Circuit 60 Hz | Operating Frequency (fsw) | 0 ... 400 Hz |
| Rated Impulse Withstand Voltage (Uimp) | Main Circuit 6 kV | Rated Insulation Voltage (Ui) | 690 V |
| Power Loss | at Rated Operating Conditions per Pole 0.6 ... 1.5 W | Number of Poles | 3P |
| Conventional Free-air Thermal Current (Ith) | Main Circuit 0.16 A | Degree of Protection | Housing IP20 Main Circuit Terminals IP10 |
| Pollution Degree | 3 | Electrical Durability | 50000 cycle |
| Mechanical Durability | 100000 cycle | Terminal Type | Screw Terminals |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm² Flexible 1/2x 0.75 ... 2.5 mm² Rigid 1/2x 1 ... 4 mm² | Tightening Torque | Main Circuit 0.8 ... 1.2 N·m |
| Wire Stripping Length | Main Circuit 9 mm | Recommended Screw Driver | M3.5 Pozidriv 2 |
| Mounting Position | 1 ... 6 | Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
| Minimum Mounting Distance | Electrical Conductive Board, Vertical 75 mm Other Device Same Type, Horizontal 9 mm Other Device Same Type, Vertical 150 mm | Actuator Type | Rotary Handle |
| Contact Position Indication | ON / OFF / TRIP | Standards | IEC/EN 60947-1 IEC/EN 60947-2 IEC/EN 60947-4-1 IEC 60335-2-40 A2L |
| Short-Circuit Current Rating (SCCR) | Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 65 kA Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 47 kA | Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
| Full Load Amps Motor Use | (120 V AC) Single Phase 0.16 A (220 ... 240 V AC) Single Phase 0.16 A | Locked Rotor Amps | (120 V AC) Single Phase 0.96 A (220 ... 240 V AC) Single Phase 0.96 A |
| Connecting Capacity Main Circuit UL/CSA | Flexible 1/2x 16-12 AWG Stranded 1/2x 16-12 AWG | Tightening Torque UL/CSA | Main Circuit 10 ... 12 in·lb |
| Ambient Air Temperature | Around the Enclosure 0 ... +40 °C Operation -25 ... +70 °C Operation Compensated -25 ... +60 °C Storage -50 ... +80 °C | Ambient Air Temperature Compensation | Yes |
| Maximum Operating Altitude Permissible | 2000 m | Resistance to Shock acc. to IEC 60068-2-27 | 11 ms Pulse 25g |
| Resistance to Vibrations | 5g 3 ... 150 Hz | Object Classification Code | F |
| ETIM 4 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. | ETIM 5 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
| ETIM 6 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. | ETIM 7 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | eClass | V11.0 : 27370409 |
| UNSPSC | 39121601 | IDEA Granular Category Code (IGCC) | 4864 >> Enclosed 3 Pole Circuit Breakers |
| E-Number (Finland) | 3707265 | E-Number (Norway) | 4364100 |
| Manufacturer ID | 1SAM340000R1001 |